Overview
About this product
The Simplex 4004-9860 adds four auxiliary relays to a 4004R releasing panel. Its outputs support application-specific trouble, alarm and release-related signaling. Relay contacts are selectable as normally open or normally closed, and a manual disconnect switch controls relays 2 through 4.
Key features
✓Four additional auxiliary relays
Auxiliary relay module with four dual-contact relays selectable as normally open or normally closed for compatible 4004R systems.
Technical specifications
| Relays | 4 dual-contact, selectable NO or NC |
|---|
| Resistive rating | 7 A at 120 VAC |
|---|
| DC inductive rating | 5 A at 30 VDC, 0.35 power factor |
|---|
| Maximum modules | 2 |
|---|
Applications
- Auxiliary relay outputs in compatible Simplex 4004R suppression release configurations.